Rev. 8/02 -1.14- TFXM
Max Loop Load = (External Supply Voltage - 5)
0.02
Cable used to transmit 4-20 mA signals should be routed in wiring
trays or conduits that carry instrumentation signals. It should not
be run with AC power or other potential sources of noise. Very
long cables can be accommodated, but the resistance of the wire
must be added to the total loop load to ensure that adequate
power is available to power the load. Shielding of the wires carry-
ing 4-20mA signals are typically not necessary, but is recom-
mended when wires must be run past or in proximity of electrically
noisy circuits.
Two independent SPDT (single-pole, double-throw, Form C)
relays are integrated into the TFXM for each measuring channel
installed within the flow meter enclosure. The relay operations are
user configured via software to act in a flow rate alarm, signal
strength alarm or totalizer/batching mode. See Figure 1.4 for ter-
minal block locations. The relays are rated for 200 Vac max. and
have a current rating of 0.5 A resistive load [175 Vdc @ 0.25 A
resistive]. It is highly recommended that a slave relay be utilized
whenever the control relays are used to control inductive loads
such as solenoids and motors.
An RS485 driver and Modbus protocol is utilized by the TFXM to
communicate between the two channels located within the TFXM
flow meter enclosure (if so equipped), communicate with satellite
TFX flow meters and to interface with a personal computer sys-
tem. The TFXM can be used as the Primary meter (Master) to
program other Secondary (Slave) meters located on the RS485
network. The TFXM contains a feature that permits up to 8 flow
measurement channels to be mathematically manipulated. Soft-
ware configuration is covered in Section 4 of this manual.
RS485 interconnections are made at the terminal block located
within the TFXM Field Wiring Access Panel. See Figure 1.4. Util-
ize two conductor plus shield wiring cable for this purpose. Avoid
running these cables in wiring trays or conduits carrying AC power
or other electrically noisy devices.
PART 1 - INPUT/OUTPUT CONFIGURATION